Technical Info - Types

Extract from 'Central Heating - Fault Finding & Repair'

Introduction
Most modern circulating pumps designed and manufactured for domestic central heating and hot water systems are suitable for either indirect open-vented or sealed type installations. There are many types of pumps with even more applications but in the domestic central heating environment there are generally just three types used.

Fixed Head Circulator
This is a circulating pump which is designed and installed to operate an often generalised type of central
heating and hot water system. It operates at one fixed speed with no adjustment available. Its operating
tolerances against head (pressure) is quite wide so the addition of an extra radiator should not cause too much of a problem.

However, an extension to a property may increase the pressure beyond its design rating. This may result in slow heat up and possibly pump failure. System noise can also be caused by one speed pumps.

Three Speed Fixed Head Circulator
The most common (currently) circulating pump is the three speed. Still with a fixed head it has a speed control for energy efficiency and more precise system matching with the consequent reduction in system noise.
Most domestic central heating boilers will not exceed 120,000 btu’s/hr (about 35 Kw) and therefore a standard 3 speed circulating pump can be used. In large domestic properties and central heating systems using micro-bore pipe work a circulating pump with a higher head should be used.
These circulating pumps tend to be set at the highest speed unless ‘pumping over’ or noise is a problem.

Automatic Variable Speed Circulators
This type of circulating pump will automatically adjust its speed to meet the pressure fluctuations caused by
differing heating demands. So as thermostatic radiator valves close in response to room temperatures the pump speed is automatically adjusted and reduces the differential pressure as the resistance of the system rises. This saves energy (electricity) and reduces the possibility of radiator valve noise.

It should be noted that circulating pumps which have an automatic speed control should not be used in central heating systems with thermostatic radiator valves fitted on every radiator unless the pump and system design and initial set up at installation ensures that the minimum flow rate through the boiler is maintained (see boiler manufacturers instructions). This is especially important as should all the thermostatic radiator valves close the pump will slow and the flow of water over the heat exchanger may not be sufficient to remove the latent heat. This can cause damage to the boiler heat exchanger or may cause noise in the boiler (kettling).

Automatic variable speed circulators must not be fitted to combination or condensing combination boilers. There are now several boilers available (fully modulating condensing boilers) that have these pumps pre-fitted by the manufacturer within the boiler casing. If this is the case do not fit an automatic by-pass. However...“Always follow the manufacturers instructions.”

Automatic Variable and Fixed Speed Circulators
This design of pump is suitable for all domestic central heating systems. It can replace most other pumps, it is easy to install and is suitable for one and two pipe radiator systems and under floor heating. It can be used with fixed or automatic by-pass valves.

Electrical Connections
There is no need to open the terminal box as they are supplied with a plug, which once wired up, attaches to the pump. Fault finding is made easier with an indicator light showing correct supply and wiring.

Automatic De-blocking
A special start up sequence of starts and stops dislodges contaminants and particles from within the pump
eliminating pump jamming.

Energy Efficiency
The pump automatically provides correct performance matching its speed to the varying heat requirements ofthe central heating system. This reduces running costs by up to 39%.

Speed
This circulating pump is able to operate at both automatic or fixed speed. Its operation is similar to the automatic variable speed circulators (see above) i.e. as the demand for heat decreases it automatically adjusts to the actual speed required, regulating the flow and pressure throughout the system. This reduces
power consumption, noise and wear and tear on the pump and system.
The pump adjusts itself to the thermostatic radiator valves required water output eliminating radiator valve noise. The fixed speed settings can be used to:
a) Help purge the central heating system of air when set on the highest fixed speed
b) Set up any fixed (manual) or automatic by-pass values when set on the lowest fixed speed

Operating Temperatures
It is especially important to ensure these automatic and fixed speed pumps are not covered with insulation/linen etc as they have a maximum ambient temperature of 35°C at 90°C system water temperatures.
DO NOT use this type of pump with combination or condensing combination boilers always follow the
manufacturers instructions.

Twin-head Circulators
Interestingly, there are now domestic circulating pumps with twin heads. They effectively replace the 3 port midposition/3 port fully diverted/2 x 2 port zone motorised valves (Y plan, W plan, and S plan respectively) system type installation.
The pump has a separate wiring centre which is connected to the boiler and controls (programmer, room and cylinder thermostats) and will simultaneously circulate water around the central heating and primary hot water systems or operate individually to meet heat demands. Each pump head has individual speed settings which means they can be set up to match the individual flow and pressure requirements of the central heating and domestic hot water system.

Extract from 'Central Heating - Fault Finding & Repair'

 

 

© 2007 Web Design by Goto Online . All rights reserved