Introduction
When
the circulating pump is first installed it will have
(should have) been set up to best match the requirement
of the central heating and hot water system. As the
system settles down there may be occasions when the
circulating pump speed needs to be adjusted e.g. new
radiators fitted, property extension/room conversion
or possibly due to system corrosion. If it is due to
system corrosion then the sludge, rust and debris need
to be removed and the system protected . It may be
that the circulating pump is reaching the end of its
working life and needs replacing.
Many circulating pumps have a manual speed selector (usually
3 speed settings) which allow for adjustment of speed
to match the requirements of the system. In other words,
the speed at which water will be circulated through the
system without creating flow noise (due to excessive
velocity), provide for an adequate flow over the boiler
heat exchanger (to prevent kettling and damage), provide
quick warm up of radiator temperatures yet give the correct
flow and return temperature differentials for maximum
efficiency. With good design practice and installation
the recommended maximum water velocity is 2 metres/second
regardless of pipe diameter. If the water velocity is
kept to approximately 1.0 metres/second for small bore
and 1.5 metres/second for micro-bore systems problems
with noise, erosion, corrosion or cavitation should not
arise.
Setting Pump Speed
The best speed setting will provide adequate circulation
and provide the correct flow and return temperature differentials
appropriate to the boiler. This will achieve maximum
economy and efficiency.
1. Set the speed selector to maximum (three). Set the
programmer to ‘CH’ on
2. Open all thermostatic radiator valves or manual radiator
valves to maximum
3. Set the room thermostat to maximum
4. The boiler and pump should start
5. After 10 minutes turn the circulating pump speed selector
to minimum (one)
6. Wait another 10–15 minutes and if the radiators
are not hot turn the circulating pump speed selector
to
the mid-setting (two)
7. Wait another 10–15 minutes and if the radiators
are still not hot set circulating pump speed selector
to
maximum (three)
Note:
a) If the speed setting is too high water noise may be
a problem
b) If the radiators get hot at different intervals the
radiator system requires balancing
Alternatively, fit an automatic and fixed speed circulating
pump. |
|