Technical Info - Position

Extract from 'Central Heating - Fault Finding & Repair'

Introduction
The position of a circulating pump is extremely important and if not correct can cause major problems with both the pump and the heating systems. The pump must be located correctly within the system and must also be correctly sited at that position.

Water Pressure
In many central heating and hot water systems the pump will be contained within the boiler housing as an integral part of the boiler. In systems where the pump is installed in the pipe work it is critical that this location is correct for that system.

In a typical open vented system that uses a feed and expansion cistern, a cold feed and expansion pipe and an open safety vent pipe there will be a pressure created by the column of water in the feed and expansion cistern and pipe work. This pressure is referred to as the ‘static head’ and is usually measured in metres. It is the vertical distance between the level of water in the cistern down to a given point in the system. Where the cold feed pipe connects into the system pipe work is the ‘neutral point.’ In systems where the cold feed and vent connect at the boiler then the boiler is the ‘neutral point.’

When the circulating pump is running it will circulate water around the system. The static pressure should not change but pressure changes will occur within the system pipe work. At the pump outlet will be positive pressure and at its inlet will be negative pressure (suction). Therefore, somewhere in the system there must be a point when the positive pressure created by the circulating pump changes to negative pressure. This point is the neutral point. It will always be at the point where the pressure cannot physically change. In open vented systems it is where the cold feed connects and in a sealed system it is where the expansion vessel is connected into the circuit pipe work. The pressure at the neutral point is either the static head generated by the column of water in the feed and expansion cistern and pipe work or the charge pressure in the expansion vessel.

From the circulating pump to the neutral point the system operates at a pressure greater (positive) than the static pressure at the neutral point. From the neutral point to the circulating pump inlet the system operates at a pressure less (negative-suction) than the static pressure.

So, locating the circulating pump in the flow pipe will have a different effect than locating it in the return. Different problems can arise depending on system design such as:

a) ‘Micro air leaks’ due to excessive negative pressure drawing air in through joints and fittings
b) Air ingress via the open safety vent pipe due to excessive negative pressure
c) Pump over through the open safety vent pipe due to excessive positive pressure

Circulating Pump Locations

Position 1
The circulating pump in the return pipe before the cold feed with the open safety vent in the flow (many older installations were designed this way), a modern replacement circulating pump may cause an increase in negative pressure. This may draw air into the system through micro-leaks in joints and fittings. This air will cause damage and corrosion to the system and its components.


Position 2

The circulating pump in the return pipe after the cold feed with the open safety vent in the flow. This may lead to ‘pump over’ unless the vent pipe has a minimum height of 1.33 x pump head. So a circulating pump head of 5 metres needs a vent pipe of at least 6.67 metres to be sure of avoiding this occurrence.
When ‘pump over’ occurs water is forced through the open safety vent pipe, due to the extra pressure created, into the feed and expansion cistern. This causes greatly increased oxygenation of the system water and rapidly leads to severe corrosion (the water is coloured rust red), system breakdown, possible water damage from overflow and increased scaling.

Position 3
The circulating pump in the flow before the open safety vent pipe with the feed and expansion pipe in the return. Again, increased pressure may cause ‘pump over.’






Position 4

The circulating pump in the flow after the open safety vent pipe with the feed and expansion pipe in the return. If the open vent pipe is high enough (1.33 x pump head) this pump location should work without problems developing. However, if the open vent pipe is not high enough see-sawing may occur.




Position 5

The circulating pump in the flow after the open vent pipe with the cold feed and expansion pipe also in the flow and before the vent pipe (but within 150mm). This is the best location and pipe layout and it is worth changing positions 1 to 4 to position 5 for increased system performance and maximum components working life.



Position 6
Where the boiler manufacturer permits (or recommends) a close coupled vent and feed arrangement. This is the best layout for modern automatic boilers. In this case the open safety vent pipe is in the flow before the circulating pump with the cold feed and expansion pipe between it and the pump. The gap between the vent and feed must be no more than 150mm (see Domestic Central Heating – 1.8). Again, always follow the boiler manufacturers recommendations.

In sealed systems the expansion vessel connection (neutral point) should be as close to the pump inlet as
possible between the pump and the boiler in the flow. This will place most of the system under positive pressureas in position 5 above. Always follow the manufacturers recommendations.

Circulating Pump Siting

Avoid siting the circulating pump:
a) At the lowest point in the system where sediment tends to accumulate. This siting may quickly lead to
circulating pump failure and unless the pump is re-sited will continue to be a source of breakdown
b) Where it touches any flammable surface or material - allow a 25mm gap
c) Where any slight vibration could cause noise
d) Close to sharp bends in the pipe work which may cause flow noise or pipe work vibration
e) In pipe work that is under tension as the tension can create noise when the circulating pump is running

Ensure the circulating pump is sited and positioned so that:

a) The terminal box is easily accessible for maintenance
b) The terminal box is not under pipe work where a leak may occur
c) The connecting pipe work is well supported with fixing brackets. This will avoid noise and possible union joint leaks
d) Connecting pipe work has a cushioning material (e.g. small squares of felt) between it and any structure
it may be touching (e.g. beams, joists etc)

Extract from 'Central Heating - Fault Finding & Repair'

 

 

© 2007 Web Design by Goto Online . All rights reserved