Extract from 'Central Heating Combination Boilers -
Fault Finding & Repair'
Introduction
When a combi boiler fires, the water in the heat exchanger
will be quickly heated. With low water content heat
exchangers the system water within the exchanger is
rapidly heated to temperature. This heated water is
needed to meet a demand from the central heating or
a domestic hot water requirement. The most efficient
way of moving this heated water to either the central
heating system or to the secondary heat exchanger is
by using a machine. This machine will circulate the
heated water to where it is needed so it can give up
its heat to meet the demand. This machine is commonly
referred to as a pump and less commonly as a circulator
or an accelerator. To cover most situations the phrase ‘domestic circulating
pump’ has been popularised.
Design & Construction
Modern quality pump construction consists of a cast
iron housing, stainless steel rotor can and rotor
cladding with ceramic upper and lower bearings, a
carbon based thrust bearing and rubber ‘O’ rings.
The terminal box is constructed of plastics. The
electric motor rotates the shaft at speeds of between
700 – 2000
rpm.
Pre-installed pumps can operate within a pressure
range of 0.1 – 10 bar (being factory tested
to 15 bar) although most combi boilers have a pre-set
maximum working pressure of 3 bar. The pumps are
designed to operate at temperatures of typically
10 – 110°C
so they can easily accommodate most conditions. In
most combi boilers the pump is installed on the central
heating return pipe.
The water contained within the pump both lubricates the
bearing and keeps the pump motor temperature within its
designed operating range. These pumps are robust and
corrosion resistant.
Many older combi boilers are fitted with a fixed
head circulating pump. This operates at one speed
and has no adjustment. Its operating tolerances against
pressure (head) is wide so suits many and varied
systems. Unfortunately it is not especially efficient
and can cause system noise. These pumps provide a
5 metre head of water with some providing a 6 metre
head.
In many modern condensing combi boilers an automatic
variable speed circulating pump is fitted. This automatically
adjusts its speed to meet the pressure fluctuations
caused by differing heating demands. As thermostatic
radiator valves close in response to set room temperatures
the pump speed automatically adjusts, reducing the
differential pressure as the resistance of the system
rises. This saves energy (electricity) and reduces
the possibility of system noise such as radiator
valve noise and pipe flow noise. When they are fitted
within the combi boiler the manufacturer may also
fit an automatic By-pass, therefore DO NOT fit an
automatic By-pass valve. Always follow the manufacturer’s
instructions.
Circulating pumps installed
by the manufacturer within the combi boiler casing
require a 230V mains supply. These pumps have a low
power consumption ranging between 35 – 100 watts,
(similar to a standard light bulb). Pre-installed
pumps are electrically protected by the combi boiler
fuse normally rated at 3 amps. The pumps are always
earthed by the combi boiler manufacturer. DO NOT
remove the terminal box cover without first disconnecting
the electric power supply and carrying out electrical
safety procedures.
Back
to the Top
Operation
As the motor rotates the shaft a circular veined wheel,
known as an impellor, draws water in through its centre
(eye) and throws it out at its edges by centrifugal
force. As the water is thrown outward it creates a
pressure drop causing more water to be drawn in at
the eye. The faster the impellor spins the greater
the centrifugal force created, which increases the
water pressure in the system.
Pumps are controlled by the time and temperature controls
of the central heating system or by flow switches (micro
switches) in the secondary hot water circuit. Circulating
pumps will pump in one direction only. The flow direction
is usually indicated with an arrow molded to the base.
If a pump is installed the wrong way around the combi
boiler will overheat and often go to lockout. ALWAYS
ensure the pump is fitted correctly.
Back
to the Top
Pump Overrun
This is a time OR temperature device which enables
the pump to continue running for a short time after
the boiler has shut down. This facility allows the
pump to continue circulating the water through the
pipe work removing the heated water from the combi
boiler heat exchanger. If the water was not circulated
the residual heat left in the exchanger would overheat
the water, possibly causing it to boil. This could
cause a noise (kettling) or cause the overheat thermostat
to operate and send the boiler to lockout. Further,
by preventing the water from over heating it reduces
the potential for scale deposition.
By providing 230V to the pump when the water is over
60°C and after the combi boiler has shut down,
the pump continues to run until the water drops below
60°C.
The thermostat/sensor is normally closed when the water
is above 60°C and opens when the
water is below 60°C.
Note: If the pump continues to run indefinitely the
thermostat/sensor or microswitch is faulty. Check the
water temperature and also check the voltage back to
the PCB.
Back
to the Top
Fault Finding
On every occasion the combi boiler fires the circulating
pump should run and when the boiler turns off the pump
will either stop immediately or will run for a short
time and then stop. When the pump runs on for a short
while it will remove latent heat from the boiler. This
is called pump ‘over-run.’ Circulating
pump faults will either be:
1. Pump failure
2. Pump speed low
3. Pump noise
Back
to the Top
Failure
There are four ways a circulating pump can fail to
start:
1. No electrical supply
1a. Faulty Capacitor
2. Worn out bearing(s)
3. Rotor seized
4. Burnt out motor windings
Back
to the Top
Electrical Supply (Faulty Capacitor)
If the pump does not start it may be there is no electrical
supply going to the pump.
1. Remove terminal cover
2. CAUTION – using a multimeter check the voltage
at the pump terminals. It should read 230V across the
brown or red (live) and blue
or black (neutral)
3. If there is no voltage the problem is at the combi
boiler (check terminals for voltage), or if the fault
is when the central heating
is calling for heat the programmer or room thermostat
is faulty.
Check setting
You can check the circulating pump has failed:
a) Turn off and electrically isolate the combi boiler
b) Remove the three wires from the pump terminals making
a note of positions
c) Using a test lead fitted with a plug and 3 Amp fuse,
connect the three wires to the pump terminals (Brown-Live,
Blue-Neutral, Green/Green and Yellow-Earth)
d) Plug the test lead into a socket
e) Switch the socket on and if the pump runs then the
fault is not with the pump but with another component
f) Remove the vent screw using the pump tool and using
a 4mm screwdriver or the pump tool, quickly spin the
rotor shaft. If the pump starts the
capacitor is leaking/faulty. Replace pumpor pump head
Note: If the pump does not start immediately turn
off the electrical supply or the pump motor (windings)
may burn out.
Back
to the Top
Worn Out Bearings
If the bearings are worn out then the pump or pump
head will need to be replaced. When checking for this
be prepared for water spillage. Protect all electrics
and electronics.

1. Turn off and electrically isolate the combi
2. Remove the vent plug in the face of the circulating
pump using a pump tool or large blade screwdriver
3. If water pours out then the bearings are worn out.
Mop up the spillage
4. Replace vent plug using pump tool or large blade
screwdriver
5. Fit new pump or pump head
Back
to the Top
Rotor Seized
The rotor may have seized due to particles of rust/sludge
or scale preventing it from
rotating. When checking for this be prepared for water
spillage. Protect all electrics and electronics.
1. Turn off and electrically isolate the combi boiler
2. Remove the vent plug in the face of the circulating
pump using pump tool. Mop up any water spillage
3. If just a few drops of water seep out fit a 4mm
screwdriver (use pump tool)
through the vent plug opening and gently turn
the shaft anti-clockwise to dislodge particles
4. If the rotor shaft feels ‘rough’ as
it spins or it will not move a new circulating pump
or pump head is required
5. If the rotor shaft turns freely (anti-clockwise)
replace the vent plug using pump tool, reconnect the
power, turn the boiler on and
check the pump is working correctly
Back
to the Top
Burnt Out Motor Windings
Having checked the electrical supply and there is 230V
at the pump terminals, the rotor has been freed and
now turns freely (anti-clockwise), but the pump does
not work, then the motor has burnt out due to the rotor
seizing and causing overheating in the motor windings.
Often, when the motor windings do burn out the 3 amp
fuse blows. Always check the fuse in the plug or fused
connection unit AND any fuse within the combi boiler.
To test and prove the motor windings have burnt out:
1. Turn off and electrically isolate the combi boiler
2. Remove pump terminal cover and remove wires to pump
terminals making a note of the connections
3. Use multimeter set on Ohms(Ω) and test the
resistance across live and neutral terminals:
Less than 1 Ohm
= Motor windings burnt out – Replace
pump or pump head
Mega Ohms/Infinity/Overload = Motor windings burnt
out – Replace pump or pump head
120 – 200 Ohms = Motor windings O.K.
Back to
the Top
Pump Speed Low
To prevent kettling and overheating, the pump must
run at speeds appropriate to the burner output level.
If the pump does slow down due to sludge/rust/debris
fouling the impellor or the pump is reaching the end
of its useful life the following may be evident:
1. Lack of heat output at radiators/domestic hot water
2. Boiler kettling
3. Frequent boiler shut down
4. Boiler cycling on limit thermostat
The debris fouling the impellor must be dislodged so
the central heating system should be drained, flushed
and protected (see Flushing & Protecting – 2.5).
If the pump is simply coming to the end of its working
life then it must be replaced.
Back
to the Top
Pump Noise
The major cause of system noise is incorrect impellor
speed. When the circulating pump speed is too slow
the following may occur:
Boiler ‘kettling’ due
to water not passing over the heat exchanger
fast enough causing it to become overheated.
Back to
the Top
Impellor
As with any central heating system component there
is wear and tear. The circulating pump will give
year after year of trouble free service but the bearings
and rotor will gradually wear and lose their precision
running ability. This ‘out of true’ state
causes the impeller to run out of balance and create
noise which is evident by the pump slightly moving
when operating. This is a sign the pump is nearing
the end of its working life and the only solution
is to fit a new pump or pump head.
Back
to the Top
Air
When air enters the pump the noise can be very loud.
It is relatively simple to vent the pump but the reason
for the air entering the system must be established
and corrected as dry running/cavitation of a circulating
pump will damage it very quickly.
If the combi boiler is installed wrongly or at the
wrong angle the top bearing may not receive system
water to both lubricate and cool it. The pump will
fail quickly if this is not corrected immediately.
Use a spirit level to check the boiler is installed
correctly.
Back
to the Top
Venting
It is essential that when a new circulating pump has
been installed, the combi boiler or the central system
system has been drained the circulating pump is vented.
It must be vented before it is allowed to start.
This will remove air and allow system water to enter.
The system water will cool the pump, preventing overheating
and will also lubricate the shaft and bearings. Permanent
damage may result from the pump being run dry even
for a short time. ALWAYS vent the pump.
Expect some water spillage so have old towels/rags
available to protect floors etc and to mop up.
1. Turn off and electrically isolate the combi boiler
2. Remove circulating pump terminal cover
3. Caution – using a multimeter check the voltage
at the pump terminals. There should be a ZERO reading
4. Replace terminal cover
5. Remove the vent plug using a pump tool or wide blade
screwdriver. Mop up water spillage
6. Fit a 4mm screwdriver (or use pump tool) through
the vent plug opening and gently turn the shaft anti
clockwise
7. Rotate the shaft several times to remove any air
8. Replace vent plug. Do not over tighten
9. Replace any fuses and turn on the electrical supply
10. Set the room thermostat to maximum
11. Set the programmer to central heating ‘on’
12. Turn on the combi boiler and check correct operation
of pump and combi boiler
13. Reset room thermostat to original setting
Back
to the Top
Pump/Pump Head Replacement
When replacing a combi boiler pump there will be water
spillage so be prepared to protect all electrics and
electronics including flooring etc and have a bowl
and old towels/rags to mop up.
1. Turn off and electrically isolate the combi boiler
2. Remove the circulating pump terminal cover
3. Caution – using a multimeter check the voltage
at the pump terminals. There should be a ZERO reading
4. Note (write it down!) the colour of each wire and
its corresponding terminal letter or number.
Brown (or red) – Live to Terminal L or 1
Blue (or black) – Neutral to Terminal N or 2
Green/Yellow (or green) – earth to Terminal E
or 3
5. Note (write it down!) the way the pump is installed
6. Note (write it down!) the water flow direction.
This is indicated by an arrow on the pump often cast
into the base of the pump
7. Remove each electric wire from its terminal
8. Drain down the central heating system or use a pipe
freezer
9. Using a pump tool remove the vent plug and deal
with any water spillage. Note the colour of the water.
If it is clear with no debris
the system water does not need to be changed. If it
is dirty (a reddish or blackish colour)
or contains debris the system MUST be flushed and protected
10.Hold the circulating pump in one hand to steady
it, loosen the union nut between the pipe work and
pump with a pipe
wrench, pliers or large spanner
10a.Alternatively, remove the pump head by using a
pump tool or a 4mm hexagonal ‘T’ bar
11. Holding the pump, completely undo both union nuts
12. Remove the circulating pump
Back
to the Top
Flushing
and Protecting the System
It is essential to minimise the possibility of future
damage or inefficient operation by ensuring the whole
system is clean and protected against corrosion.
Back
to the Top
Fitting the New Pump
Circulating pumps should be replaced either on a like
for like basis, if available, or leading manufacturers
provide replacement guides and fitting kits/recommendations
for using their pumps.
1. Do not apply sealants or jointing compounds to any
surface including the threads of the isolating valves
or the pump port threads. Assemble
dry
2. With the flow arrow in the correct direction (check
your notes) place the new circulating pump into position
between the union nuts
3. Slide the new gaskets into place
4. Hand tighten both union nuts ensuring the gaskets
do not move out of position
5. Steady the new circulating pump with one hand and
tighten both union nuts. Do not over tighten. Ensure
the pump is at the correct
angles
6. Important – vent the circulating pump
7. Remove the terminal cover and using your notes rewire
the new circulating pump
8. Replace the terminal cover
9. Replace any fuses and turn on the electrical supply
10. Set the room thermostat to maximum
11. Set the programmer to central heating ‘on’
12. Turn on the combi boiler
Back
to the Top
Fault Finding
No Central Heating/No Hot Water
Reason
Pump failure – no electrical supply.
Pump failure – burnt out motor windings.
Pump failure – rotor seized due to
rust/sludge sediment
Pump failure – worn out bearing(s)
due to wear and tear
Pump failed – dry running
Pump failed - impellor broken from shaft
Pump failure – burnt out motor
windings due to seized rotor
Pump capacitor faulty
No Central Heating/Hot Water O.K.
Reason
Room thermostat faulty so no signal to
combi boiler
Diverter valve faulty
No Hot Water/Central Heating O.K.
Reason
Diverter valve faulty
Insufficient Heat To Radiators
Reason
Pump speed slow due to
sediment/sludge etc
Frequent Combi Boiler Shut Down
Reason
Pump speed slow due to sediment
causing combi limit thermostat to activate
Pump Noise
Reason
Air in system/pump
Dry running of pump
Impellor out of balance due to wear and tear
Pump buzzing due to selector switch set midway
between settings
Pump buzzing due to jammed rotor
Pump Overrun
Reason
Faulty water temperature thermostat/ sensor or
faulty microswitch |
Repair
Check electrical connections at pump.
Replace pump head.
Repair impellor movement or replace pump or pump
head.
Replace pump head.
Replace pump head and vent before turning on combi
boiler
Replace pump/pump head
Replace pump/pump head
Test capacitor and replace if faulty or replace
pump/pump head
Repair
Check call for heat at room thermostat
Check diverter valve
Repair
Check diverter valve
Repair
Drain, flush and protect system and overhaul pump
Repair
Flush and protect system and overhaul pump
Repair
Vent system and pump
Position combi boiler correctly
Replace pump head
Reset to the higher speed
Free the rotor or replace pump/pump head
Repair
Measure water temperature. If less than 60°C
and voltage from thermostat/sensor or microswitch
to PCB then check thermostat or microswitch
|
Back
to the Top
Service & Repair
Circulating pumps should give many years of quiet efficient
hot water circulation. They are precision manufactured
to a high quality standard and are robust and resistant
to corrosion. They may seize if the system water
contains corrosive particles of rust and sludge.
After long periods of non-operation, rust and sludge
sediment may settle within the body which cause the
pump to seize when first started. Therefore, before
the pump is started it is good practice to remove the
vent plug and rotate the shaft using a small screwdriver
or pump tool. Continue to spin the shaft until it runs
freely, replace the vent plug and turn on the combi
boiler.
Back to the Top
Circulating Pump Overhaul
Most modern pumps can be overhauled for cleaning etc.
Note that the following procedure DOES NOT form part
of an annual service:
1. Turn off the boiler
2. Turn off the electrical supply to the boiler and
pump, remove plug(s), fuse(s)
and put them in your pocket,etc.
3. Remove circulating pump terminal cover
4. Caution – using a multimeter check the voltage
at the pump terminals. There
should be a ZERO reading
5. Drain down the central heating system or use a pipe
freezer
6. Unscrew the four bolts holding the pump head to
its base using a pump tool
or a 4mm hexagonal ‘T’ bar
7. Carefully pull the circulating pump head forward.
Mop up water spills
8. If the water is red or black or contains debris
the whole central heating system must be flushed and
protected
9. Carefully place a flat-head screwdriver between
the bearing plate and rubber gasket. Do not try to
lever off the impellor
10.Carefully lever around the circumference between
the bearing plate and the rubber gasket. This will
withdraw the rotor
can and the rotor/impellor assembly
11.Tap the end of the rotor shaft to remove the rotor/impellor
assembly from the rotor can
12.Completely remove the rotor/impellor assembly
13.Using a detergent mixture clean the rotor and shaft
and the inside of the rotor can
14.Rinse thoroughly. Protect electrical components
from water
Back
to theTop
Re-Assembly
1. Refit the rotor can into the motor head. Ensure
the rubber upper sealing ring is in place at the top
of the can
2. Fit the lower rubber gasket onto the rotor can and
lightly position the rotor assembly into the rotor
can
3. Re-fit the head to the pump base and hand tighten
the four bolts
4. Fully tighten the four bolts in turn diagonally
a little at a time, this will pull the assembly into
position
5. Remove pipe freezer and allow ice plugs to melt
6. Check the rotor movement, using a pump tool or 3mm
screwdriver place the tip in the end of the slot of
the rotor. Make sure it moves
freely
7. Replace the vent plug
8. Replace terminal cover
9. Replace any fuses and turn on the electrical supply
10. Set the programmer to central heating ‘on’
11. Turn on the combi boiler
12. Reset room thermostat to original setting
Extract from 'Central Heating Combination Boilers -
Fault Finding & Repair'
|